Wacker Neuson G50(T4i)

Double tap to zoom

 

Features

  • Ideally suited for construction sites where durability, reliability and flexibility are required to supply continuous power for applications such as lighting, cranes, concrete mixers and conveyor belts.
  • Brush-less, oversized alternators with separate excitation winding and AVR (Automatic Voltage Regulation) provide superior motor starting and enhanced ability to run non-linear loads.
  • Single switch start and simple, uncluttered control panel provide unmatched ease of use.
  • Automatic remote start capability standard which is ideal for temporary standby applications.
  • Factory-installed customized options are available. These include, but are not limited to, a fluid containment system, cold weather options, a cam-lock panel, etc. Also available are optional trailers that are fully equipped and highway ready.

Specifications

GT50 (T4i)
Dimensions
L x W x H Operating (Skid) in 96.25 x 38 x 53
L x W x H Shipping (Skid) in 100 x 40.5 x 65.1
L x W x H Shipping/Operating (Trailer) in 160 x 67.5 x 80
Weights
Weight Dry (Skid) lb 3,178
Weight Operating (Skid) lb 3,783
Weight Shipping (Skid) lb 3,334
Weight Operating (Trailer) lb 4,663
Weight Shipping (Trailer) lb 4,058.2
Operating data
Trailer coupling Type Pintle
Standby output kW 42
Prime output kW 38
Voltage 3 Phase V 240 / 480
Current 3 Phase (Prime) A 114 / 57
Current 1 Phase (Prime) A 120 / 240
Voltage 3 Phase V 208, 220, 240, 416, 440, 480
Voltage 1 Phase V 120, 127, 139, 240, 254, 277
Circuit breaker (Main) A 175
Frequency Hz 60
Power factor 1 Phase cos Φ 1~ 1
Power factor 3 Phase cos Φ 3~ 0.8
Sound level (LwA) at Prime (23 ft / 7 m) dB(A) 67.2
Receptacles -20 Amp GFI Duplex 2
Receptacles -50 Amp Twist Lock 3
Engine / Motor
Engine / Motor Liquid-Cooled, 4 Cylinder
Engine / Motor manufacturer John Deere
Emissions Certified Tier 4i
Displacement in³ 275
Operating performance SAE J1349 hp  
Operating performance SAE J1995, ISO 8528-1 hp 74
at rpm rpm 1,800
Coolant Capacity US qt 20
Engine oil Capacity US qt 15.9
Fuel type Diesel
Fuel consumption (Prime Load) US gal/h 3.4
Tank capacity -Fuel US gal 84
Quantity (Battery) 1
Battery V 12
Generator model Mecc Alte, Brushless w/AVR
Voltage control No Load to Full Load +/- % 1
Voltage control Steady State +/- % 0.2
Generator insulation (class) H
Frequency (Generator Speed) Hz 60
Runtime at 100% Prime Load h 21.6
Runtime at 75% Prime Load h 27.2
Runtime at 50% Prime Load h 38.4
Runtime at 25% Prime Load h 64.5

Would you like more information?