Generac Mobile Products MMG45IF4 Diesel Generator

No Image Available
No Image Available

 

Features

DURABLE

  • EPA Tier IV Turbocharged, after-cooled diesel engine
  • 3 position selector switch for power output flexibility
  • Long-run time – 27 hours
  • Rust-proof, aluminum enclosure

 

EASY TO USE

  • Power Zone™ controller and display
  • Push buttons for easy operation
  • Voltage adjustment integrated into Power Zone controller
  • Aluminum, sound attenuated enclosure – 65dB (A)

 

SAFE

  • 9 warning and shutdown features
  • Lockable control box door with diagnostics window
  • Lockable lug box with safety switch
  • Emergency stop switch located on outside of enclosure
  • Central lifting point
  • 120% Containment

Specifications

ENGINE

  • Isuzu® 4LE2XAGV01 - turbocharged, aftercooled diesel engine 
    o Prime – 57 hp, 42.8kWm @ 1800 rpm
    o Standby – 63.7 hp, 47.5 kWm @ 1800 rpm
    o 4 cylinder o 2.2 L displacement 
    o EPA Final Tier 4 approved
    o *Engine and generator performance are dependent upon 70 hours of break in.
  • Polyethylene, single wall fuel tank
    o 100 gal. (378.5 L) capacity
    o 27 hr. run time – full load o Fuel tank built into skid of generator set
    o 120% Containment
  • Cooling system capable of operating at 120°F (49°C) ambient
  • Radiator and oil drains plumbed to exterior
  • Rubber vibration dampers isolate engine/generator from frame
  • Disposable air filter - paper element • Air cleaner restriction indicator
  • 60 Hz engine/generator
  • Electronic isochronous governing • Idle switch

 

GENERATOR

  • Marathon Electric® SUPERSTART™
    o Brushless o 4 pole
    o Class H insulation
  • Voltage regulation +/- 0.5% with Magnum PM600 Voltage Regulator

 

SYSTEM OUTPUTS

  • 3 position selector switch
    o Single phase – 120 / 240V Zig Zag
    o Three phase – 120 / 208V Low Wye
    o Three phase – 277 / 480V High Wye
  • 33 kW / 33 kVA – standby, single phase
  • 30 kW / 30 kVA – prime, single phase
  • 40 kW / 50 kVA – standby, three phase
  • 36 kW / 45 kVA – prime, three phase

 

SYSTEM CONTROLS

  • Power Zone® controller and display
    o Backlit, 800 x 480 pixel resolution color display
    o -40°F to 185°F (-40°C to 85°C) operating temperature range
    o Automatic coarse voltage adjustment
    o Integrated fine voltage adjustment
    o PLC functionality
  • Push buttons for easy operation
    o Manual or Auto Start
    o Engine Start
  • o Engine Stop/Reset
    o Alarm Mute
    o Operator Screens
       • Home
       • Engine 
       • Generator 
       • Voltage Adjust
    o Scrolling Arrows for Diagnostic Information 
       • Engine diagnostic display
          • Oil pressure
          • Engine temperature
          • Fuel level
          • Battery
          • After treatment inlet/outlet temperature
          • Ash/soot levels
       • Generator diagnostic display
          • System kW output display
          • Line output & frequency display
       • Alarms
         • Warning
         • Shutdown
         • Electrical Trip
         • Engine
       • Alarm list – warnings / shutdowns; 250 event history log – date/time stamp
         • Fuel level: warning – 15%; shutdown – 5% 
         • Over speed protection: shutdown – 115%
         • Oil pressure: warning – 25 psi; shutdown – 20 psi
         • Coolant temperature: warning – 220°F (104°C); shutdown – 230°F (110°C)
         • Battery voltage: over – 15VDC; under – 11VDC
         • Generator over voltage: warning – 110%; electrical trip – 111%
         • Generator under voltage: warning – 87%; electrical trip – 86%
         • Generator over frequency: warning – 105%; electrical trip – 110%
         • Generator under frequency: warning – 95%; electrical trip – 90%
         • Inputs/Outputs 
         • Auto Schedule 
         • Status
         • Configuration of controller, firmware and connections

 

ELECTRICAL CONTROLS

  •  Remote start / stop contacts located in lug box
  • Lockable control box door with diagnostics window
  • Lockable lug box with safety switch
    o Trips main breaker when door is opened
    o Disables voltage regulator
  • Output ground connection lug inside lug box
  • 225A main breaker with shunt trip
  • Convenience receptacles with individual breakers (restricted use in high wye mode)
    o (2) 120V 20 Amp GFCI duplex outlets – (NEMA 5-20R type)
    o (3) 125 / 250V 50 Amp, 3 pole, 4 wire Twistlock (Non-NEMA 6369)
  • Voltage adjustment integrated into Power Zone controller, +/- 10%
  • 720 CCA wet cell battery 
  • Battery disconnect
  • Panel lighting for breakers, lugs, and selector switch

 

ENCLOSURE

  • Aluminum, sound attenuated enclosure
    o UV & fade resistant, high temperature cured, white polyester powder paint
    o Insulated and baffled
    o 65 dB(A) at 23 ft. (7 m) – prime power
  • Fully lockable enclosure including doors and fuel fill
  • Emergency stop switch located on outside of enclosure
  • Central lifting point • Multi-lingual operating/safety decals
  • Document holder with operating manual including AC/DC wiring diagrams 
  • Interior Cabinet lighting

 

TRAILER

  • DOT approved tail, side, brake, and directional lights - LED
  • Transportation tie downs
  • Safety chains with spring loaded safety hooks
  • 2 in. (50.8 mm) ball hitch
  • 5000 lb. (2268 kg) axle 
  • 2000 lb. (907 kg) tongue jack with footplate 
  • P225/75 R15 tubeless tires – 6 ply